FIRE BARRIER TEST
on
FBS® System-ELECTRICAL CONDUIT
ASTM
119-98 Fire Retardant Test at OMEGA
LABS
Flame Seal ®
FBS®
Fire Barrier System
by FLAME SEAL
PRODUCTS, INC.
(713) 668 4291 office, (713) 668 1724 fax.
ASTM E 119-98
Fire Tests of Building
Construction and Materials
Protection of Electrical Raceways
Project No. 14770-104554
FIBERGLASS CONDUIT PROTECTED BY FLAME
SEAL'S “FBS®-
60 PROTECTIVE SYSTEM”
.
April 7, 1999
.
Prepared For:
Flame Seal Products, Inc.
4025 Willowbend Blvd., Suite 310
Houston, TX 77025
.
ABSTRACT
A 4” fiberglass electrical conduit, filled with a combination of
power,
control, and instrumentation cables was instrumented with
thermocouples,
covered with Flame Seal Products “FBS-60 Protective System”, and tested
in accordance with ASTM E119-98 Standard Test Methods for Fire
Tests
of Building Construction and Materials. Under the test conditions
described,
the system evaluated successfully protected the conduit test article
for
a fire resistance period of 60 minutes.
| This report is for the exclusive use of the client named herein. Omega Point Laboratories, Inc. authorizes the client to reproduce this report only if reproduced in its entirety. The test specimen identification is as provided by the client and Omega Point Laboratories, Inc. accepts no responsibility for any inaccuracies therein. The description of the test procedure, as well as the observations and results obtained, contained herein are true and accurate within the limits of sound engineering practice. These results are valid only for the specimens tested and may not represent the performance of other specimens from the same or other production lots. This report does not imply certification of the product by Omega Point Laboratories, Inc. Any use of the Omega Point Laboratories name, any abbreviation thereof or any logo, mark, or symbol therefor, for advertising material must be approved in writing in advance by Omega Point Laboratories, Inc. The client must have entered into and be actively participating in a Listing & Follow-up Service program. Products must bear labels with the Omega Point Laboratories Certification Mark to demonstrate acceptance by Omega Point Laboratories, Inc. into the Listing Program. |
Michael E . Dey
Reviewed and approved:
William E .Fitch, P.E. No. 55296 Date 4/5/99
OMEGA Point Laboratories, Inc.
16015 Shady Falls Road
Elmendorf, Texas 78112-9784
210-635-8100/Fax: 210-635-8101/ 800-966-5253
www.opl.com/ e-mail: moreinfo@op.com
| Flame
Seal Products,
Inc.
April 7, 1999 Project No. 14770-104554 Page iii |
||||||||||||||||||||
|
|
||||||||||||||||||||
ITEM PAGE
|
INTRODUCTION
The protection of vital electrical circuits from the effects of an external fire exposure is of primary concern in the design and construction of an electrical power generating plant. Typical “fire protective envelopes” are designed to protect the contents of an electrical raceway for fire exposure periods of one to three hours.
The external fire exposure selected to evaluate this protective envelope system is that described in the ASTM E119-98 Fire Tests of Building Construction and Materials (E119 Time-Temperature Curve, described later in this document.)
Typical fire test programs involve the selection and construction of a specific electrical raceway system, instrumentation for thermal measurements, followed by the application of the fire resistive barrier system by qualified personnel.
This standard should be used to measure and describe the properties of materials, products, or assemblies in response to heat and flame under controlled laboratory conditions and should not be used to describe or appraise the fire hazard or risk of materials, products, or assemblies under actual fire conditions. However, results of this test my be used as elements of a fire risk assessment that takes into account all the factors that are pertinent to an assessment of the fire hazard of a particular end use.
TEST PROCEDURE
The test furnace used consists of a large horizontal exposure chamber, with internal dimensions of 12 ft (length) by aft (width). The furnace is equipped with diffuse-flame propane gas burners symmetrically located across the floor of the furnace and controlled by individual gas flow valves, with the overall gas flow to valves, with the overall gas flow to the furnace being controlled by a single gas control valve. Capable of a maximum heat output of 5 million Btu/hour, these burners are arranged well below the exposed face of the specimen to ensure an even temperature at the surface of the specimen. Windows are located on two sides of the furnace to allow observation of the specimen during fire exposure. The depth of the furnace is variable, being increased to the desired amount by the addition of concrete blocks around the perimeter ledge. These blocks are lined with ceramic fiber blanket to minimize the heat loss from the furnace and to decrease the time required for the furnace walls to heat up.
The temperature within the furnace is determined to be the mathematical average of thermocouples located symmetrically within the furnace and positioned twelve inches away from the exposed face of the test specimen. The materials used in the construction of these thermocouples are those suggested in the test standard. During the performance of a fire exposure test, the furnace temperatures are monitored at least every 15 seconds and displayed for the furnace operator to allow control along the specified temperature curve.
The fire exposure is controlled to conform with the standard
time-temperature
curve shown in the table below:
|
(min) |
(°F) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
The fire test is controlled according to the standard time-temperature curves as indicated by average temperature obtained from the readings of the furnace interior thermocouples symmetrically located across the specimen, 12 in. away. The thermocouples are enclosed in protection tubes of such material and dimensions that the time constant of the thermocouple assembly lies between 5.0 and 7.2 minutes, as required by the E 119 standard. The furnace temperature during a test is controlled such that the area under the time-temperature curve is within 5% of the corresponding area under the standard time-temperature curve for the three-hour test period.
The furnace pressure is controlled to be as nearly neutral with respect to the surrounding laboratory atmosphere as possible, measured at the vertical mid-height of the test specimen.
Conditions of Acceptance
The fire endurance rating of a fire-resistive barrier system for a specific electrical system component is the maximum time before which one of the following conditions occurs:
The average temperature of any set of thermocouples for the
electrical
system component
is raised more than 250° F (139° C) above its initial
temperature.
The temperature of any one thermocouple of the set for each electrical
system component
is raised more than 325°F (181°C) above its initial
temperature.
Systems reaching either of these criteria, or which are terminated,
at times other than even-hour time periods shall be rated to the 15-min
increment immediately preceding the time at which the criteria
condition
or termination occurred.
TEST SPECIMEN CONSTRUCTION
A 4” fiberglass electrical conduit (10 ft. long with 1/6 “ wall
thickness)
was purchased by Flame Seal Products and delivered to the Laboratory.
Prior
to the installation of the fire protective system, the conduit was
filled
to an actual cross-sectional fill of 40. 0% with the following mix of
cables.
All cables were XHHW copper conductors.
|
|
(inches) |
(in²) |
CABLES |
(in²) |
|
(4/C # 16 AWG) |
|
|
|
|
|
(7/C #12 AWG) |
|
|
|
|
|
(3/C # 6 AWG) |
|
|
|
|
Barrier Installation
The protective envelope system was supplied and installed by representatives of Flame Seal Products, Inc., and the following description of that system was supplied by the client. While complete verification of the system was not possible, since the components were pre-assembled, no obvious deviation from these details was noticed.
The system was a two-layered version of Flame Seals FBS System. It consisted of the following components:
1) Standard FBS with a 2 mil stainless steel foil outer surface.
Dimensions
per piece = 11” x 24” (two pieces per section). Weight = 6.5 lbs.
each
(3.55 lbs./sq.ft.).
2) ½ inch thick ceramic wool blanket glued to 2-mil aluminum
foil with Flame Seals FX-FBS adhesive. Dimensions per piece=17” by 21
“(one
piece per section). Weight=0.35 lbs./sq. ft.
3) 4” wide strips of thin FBS flat stock used at joints, for all butt
joints.
4) 3” wide strips of stainless steel foil and fiberglass laminated
with FX-FBS adhesive.
5) Stainless steel hog rings, every ½” to ¾” at all
joints.
6) Aluminum Tape.
Installation was as follows:
A) 4” strips were “coil” wrapped and taped 3 layers thick on 24”
centers
located under the joints between sections.
B) Foil faced ½” ceramic wool pieces (#2 above) were wrapped
around the conduit between these joint strips and taped in place
with aluminum tape
C)FBS- 60 was located with the ends centered on the joint strips (“A”
above), wrapped tightly over the ceramic wool layer and hog ringed in
place
along all seams formed by junctions between pieces.
D)Butt joints were covered with a 3” wide stainless steel foil and
fiberglass laminated and hog-ringed in place.
E) Aluminum tape was installed over the hog-ringed seams.
The completed ten foot long test article was sealed on both ends of the conduit, to stop any heat from escaping, placed on the ledges of a fire resistance furnace which exposed a minimum of 84 inches to the heat. The ledges of the furnace were then built up with concrete block to a minimum of 18 inches above the top of the test article, and an insulated lid was placed on top to complete the furnace assembly.
TEST RESULTS AND OBSERVATIONS
The test item was placed across the Laboratory's intermediate-scale horizontal furnace (as described earlier) and all thermocouples connected to the data acquisition system and their outputs verified. Photographs were taken, the furnace thermocouple positions checked, and the furnace was fired at approximately 2:25 p.m. on March 19, 1999. The ambient temperature was 69 F and the relative humidity was 60%. The furnace pressure was maintained so that the neutral pressure plane was at the vertical mid-height of the specimen. The test procedure was witnessed by Michael Kiser of Flame Seal Products, Inc.
Observations made during the test
are
as follows:
|
|
|
| 0:00 | Furnace Fired |
| 0:56 | Char forming at joints. |
| 2:26 | Stainless steel foil is entirely black. |
| 8:45 | Full expansion of system between joints with some constriction at the joints. |
| 29:00 | No change. |
| 43:00 | Conduit slightly bowed in middle. |
| 60:00 | Furnace extinguished. |
THERMOCOUPLES
All temperatures monitored within the test specimen were measured using 24 ga., electrically-welded thermojunctions, Type K Chromel-Alumel, Fiberglass Insulated (Special Limits of Error: +1.1° C) thermocouples, purchased with calibration certifications and lot traceability.
The thermocouple locations can be found in Appendix A.
A summary of the thermocouple data is given in the table below:
INDIVIDUAL TCs AVERAGE TCs
|
|
TEMP (°F) |
ALLOWED (°F) |
TEMP (°F) |
ALLOWED (°F) |
(min) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Cables |
|
|
|
|
|
Listing and plots of the furnace control temperatures and specimen temperatures may be found in Appendix B. A photographic documentation of the test has been included in Appendix C.
CONCLUSIONS
At the end of the 60-minute fire exposure, the highest temperature on the entire test article was 290F. All temperatures remained well below the maximum allowable limits for the entire test duration. The 4” fiberglass electrical raceway protected by Flame Seal Products’ FBS-60 Protective Systems” and evaluated by this Laboratory achieved a rating of 60 minutes.
Appendix A
THERMOCOUPLE LOCATIONS
| Flame
Seal Products,
Inc.
April 7, 1999 Project No. 14770-104554 Page 8 |
|
|
| Note: The 4” fiberglass electrical conduit was instrumented with 13 thermocouples along the bottom surface, as indicated. The TCs were mounted on the outside of each rail by covering with a single layer of fiberglass electrical tape. The conduit was loaded with a mixture of power (3/C#6 AWG, 4 pieces), control (7/C#12 AWG, 5 pieces) and instrumentation (4/C#16AWG, 14 pieces) cables to an actual cross-sectional fill of 40%. One cable of each type was instrumented with thermocouples every 6” o/c., attached with a single layer of electrical tape. All cables were then randomly placed into a bundle and pulled through the conduit. All cables were types XHHW with copper conductors. |
|
|
Scale: 1/2" = 1"
|
|
Page 9
|
| Flame
Seal Products,
Inc.
April 7, 1999 Project No. 14770-104554 APPENDICES |
|
|
|
|
|
|
|
Page 10
|
|
Project No. 14770-104554 Conduit Surface Temperatures |
|
|
|
|
|
Page 11
|
|
Project No. 14770-104554 Power Cable Temperatures |
|
|
|
|
|
Page 12
|
|
Project No. 14770-104554 Control Cable Temperatures |
|
|
|
|
|
Page 13
|
|
Project No. 14770-104554 Instrumentation Cable Temperatures |
|
|
|
|
Page 14 - Page 31 are Temperature Measurement Charts at all thermocouple readings shown on graphs illustrated on Pages 10 - 13 - Available on Request
|
Page 32
|
| Flame
Seal Products,
Inc.
April 7, 1999 Project No. 14770-104554 APPENDICES |
|
PHOTOGRAPHS
|
|
|
|
Page 33
|
|
| Flame Seal Products, Inc. Project No. 14770-104554 |
April 7, 1999
APPENDICES
|
|
|
|
| 4" Strips taped three layers thick located under joints between sections |
|
|
Page 34
|
|
| Flame Seal Products, Inc Project No. 14770-104554 |
APRIL 7, 1999
APPENDICES
|
|
|
|
|
|
|
|
|
|
Page 35
|
|
| Flame Seal Products, Inc. Project No. 14770-104554 |
April 7, 1999
APPENDICES
|
| Installation complete except for sealing the ends | Installation complete (The system evaluated in this report is on the right) |
|
|
|
Page 36
|
|
| Flame Seal Products, Inc Project No. 14770-104554 |
April 7, 1999
APPENDICES
|
![]() |
|
|
(The system evaluated in this report is at the top) |
|
|
|
|
APPENDICES
Page 37
|
| Flame Seal Products, Inc. Project No. 14770-104554 |
| Lid removed after the end of the fire exposure. (The System Evaluated in this report is at the top) |
|
|
END OF REPORT
ASTM E119-98
FIRE TESTS OF BUILDING
CONSTRUCTION AND MATERIALS
PROTECTION OF ELECTRICAL RACEWAYS.
| ADDRESS:
FLAME SEAL PRODUCTS, INC.
4025 Willowbend Blvd. # 310, Houston, Texas, 77025 USA, (713) 668
4291 office, (713) 668 1724 fax, Website: www.flameseal.com
Email: flameseal@flameseal.com |
| PRODUCTS:
BARRIERS: | FBS Wrap -Cables, Conduits, Flanges | FBS Panel -Walls | LIQUIDS: | Wood | Leather | Fabric | Coating | Plastic | Paper | Wild Fire Coating | GENERAL | Prices | Product Description | Products | Testing Info | MSDS Index | In the Lab - NEW PRODUCTS ! | Privacy Policy | ( Investment: | Stock News | Transfer Agent | ) |