March 2,
2000
Michael
Kiser
Flame Seal Products
NEW ADDRESS
4025 Willowbend Blvd. Suite 310
15200 WEST DRIVE
Houston Tx 77025
HOUSTON TX
77053 USA
Re:
Project No. 14770-105723
ASTM E 119-98 Fire Tests of Building
Construction and Materials
Dear Mr.
Kiser:
This
letter represents an interim report of the results from your FBS®
“ Single Layered” System for Wall Structures test performed
on October 13, 1999.
The test
assembly consisted of Insulated Panel Systems’ TecFoam ™
IPP Partition Panels (3 “thick with a rigid modified isocyanurate
core and white polyester 26 GA. Steel facers on both sides) installed
in a 10¢ x 10¢masonry lined frame and covered with Flame Seal
Products¢ FBS®--SL system. Both the foam core panels and the
FBS®-SL system were produced without the benefit of third party
inspection. Upon completion of the installation, the test assembly was
mounted against the laboratory’s vertical full scale test
furnace, the burners were fired, and the ASTM E 119-98 time/temperature
curve was followed for a period of 120 minutes. The lab ambient
temperature at the start of the test was 89°F and the relative
humidity was 42%. After 118 minutes of fire exposure, a thermocouple on
the cold side of the assembly exceeded the maximum allowable
temperature of 414°F.
A test
assembly of identical construction was previously tested at the Omega
Point Laboratories, Inc. on July 21, 1999. That test was terminated
after 79 minutes to be utilized as a hose stream retest sample. After
the 79 minute fire exposure, the wall was exposed to the standard hose
stream test for a period of 150 seconds at a pressure of 90 psi from 20
feet way from the exposed surface. The water washed all of the FBS-SL
off the exposed side of the wall, but did not penetrate foam wall
panels, which remained firmly in place.
In
conclusion , the foam core wall panel system protected by Flame Seal
Products, Inc. FBS®” SINGLE LAYERED” FOR WALL
STRUCTURES tested as described in this letter, successfully met the
conditions of acceptance as outlined in ASTM E 119-98 Fire Tests of
Building construction and Materials for a fire endurance rating of 118
minutes.
Thank
you for your continued interest in our fire and flammability testing
services.
If you require anything else with
regard to this project, don’t hesitate to call. We appreciate
business and look forward to working with you again soon.
Sincerely,
Michael
E. Dey
Fire Test Technologist
Omega
Point Laboratories, Inc.
16015 Shady Falls Road
Elmendorf, Texas 78112-9784
210-635-8100/ Fax:210-635-8101/
800-966-5253
Flame Seal Products, Inc.
Project No. 14770-105723
Furnace Interior Temperatures