FBS
®  FIRE BARRIER TEST conducted by Flame Seal Products- 2 HOUR TEST
"THE ABSOLUTE BEST IN FIRE PROTECTION TECHNOLOGY"
 |  FBS® FIRE BARRIER SYSTEM WRAP  |  FBS® FIRE  BARRIER SYSTEM  PANEL
Flame
                                    Seal Home Pg
Fire Retardant Types
Distributors Button
Fire Codes Passed
Company News Releases
Company Privacy Policy
Mission Policy

 ® FIRE PROTECTIVE COATING by Flame Seal ®


The Average Cold Side Temperature of the Test Wall may not exceed 328°F.
Temperature Readings for the Panel test :

Furnace Test Temperatures at Omega Laboratories  met the required Furnace Interior Temperature Requirements:



March 2, 2000

Michael Kiser
Flame Seal Products                       NEW ADDRESS
4025 Willowbend Blvd. Suite  310     15200 WEST DRIVE
Houston Tx 77025                                  HOUSTON  TX  77053  USA

Re: Project No. 14770-105723
ASTM E 119-98 Fire Tests of Building Construction and Materials

Dear Mr. Kiser:

This letter represents an interim report of the results from your FBS® “ Single Layered” System for Wall Structures test performed on October 13, 1999.

The test assembly consisted of Insulated Panel Systems’ TecFoam ™ IPP Partition Panels (3 “thick with a rigid modified isocyanurate core and white polyester 26 GA. Steel facers on both sides) installed in a 10¢ x 10¢masonry lined frame and covered with Flame Seal Products¢ FBS®--SL system. Both the foam core panels and the FBS®-SL system were produced without the benefit of third party inspection. Upon completion of the installation, the test assembly was mounted against the laboratory’s vertical full scale test furnace, the burners were fired, and the ASTM E 119-98 time/temperature curve was followed for a period of 120 minutes. The lab ambient temperature at the start of the test was 89°F and the relative humidity was 42%. After 118 minutes of fire exposure, a thermocouple on the cold side of the assembly exceeded the maximum allowable temperature of 414°F.

A test assembly of identical construction was previously tested at the Omega Point Laboratories, Inc. on July 21, 1999. That test was terminated after 79 minutes to be utilized as a hose stream retest sample. After the 79 minute fire exposure, the wall was exposed to the standard hose stream test for a period of 150 seconds at a pressure of 90 psi from 20 feet way from the exposed surface. The water washed all of the FBS-SL off the exposed side of the wall, but did not penetrate foam wall panels, which remained firmly in place.

In conclusion , the foam core wall panel system protected by Flame Seal Products, Inc. FBS®” SINGLE LAYERED” FOR WALL STRUCTURES tested as described in this letter, successfully met the conditions of acceptance as outlined in ASTM E 119-98 Fire Tests of Building construction and Materials for a fire endurance rating of 118 minutes.

Thank you for your continued interest in our fire and flammability testing services.
If you require anything else with regard to this project, don’t hesitate to call. We appreciate business and look forward to working with you again soon.

Sincerely,

Michael E. Dey
Fire Test Technologist

Omega Point Laboratories, Inc.
16015 Shady Falls Road
Elmendorf, Texas 78112-9784
210-635-8100/ Fax:210-635-8101/ 800-966-5253


Flame Seal Products, Inc.
Project No. 14770-105723
Furnace Interior Temperatures
.




Flame Seal Products, Inc.
Project No. 14770-105723
Min, Avg, Max Cold Side Temperatures



Flame Seal Products, Inc.
Project No. 14770-105723
Furnace Interior Temperatures


 


 