PAPER FIRE RETARDANT TEST - NFPA 701
THE
ABSOLUTE BEST IN FIRE
PROTECTION
TECHNOLOGY ™
|







|

October 18, 2005
FLAME SEAL PRODUCTS INC.
4025 Willowbend Blvd., #310
Houston, TX 77025
Reference: Laboratory Test
Report
Lab
Identification No. 5634
Invoice No. 8471
One (1) paper sample, identified as 30 LB.
KRAFT
PAPER
TREATED WITH “PAPER SEAL” PRODUCT, was received and tested in
accordance with
the National Fire Prevention
Association No. 701, “Standard Methods of
Fire
Tests for Flame Propagation of Textiles and Films, 2004 Edition,
(Test 1, Small
Scale)”. The results are as follows:
| Specimen Number |
Residual Flame (seconds) |
Weight Loss (percent) |
1
|
0.0 |
22.45 |
2
|
0.0
|
20.93 |
3
|
0.0
|
22.91
|
4
|
0.0
|
23.45 |
5
|
0.0
|
23.09
|
6
|
0.0
|
24.31
|
7
|
0.0 |
26.60 |
8
|
0.0
|
26.45
|
9
|
0.0 |
26.36 |
10
|
0.0
|
38.27 |
|
AVG.
|
----------
0.0 |
----------
25.48 |
The
paper
sample submitted meets
the minimum
requirements of the above standard. The average percent weight loss
cannot
exceed 10% and the weight loss of individual specimens cannot exceed
mean value
plus three standard deviations. The average residual flame cannot
exceed 2.0
seconds.
If
there are any questions or when we can be of
further
assistance, please let us know.
Sincerely,
Bobby E. Puett
BEP/m
|
|
FLAME SEAL
PRODUCTS, INC. 4025 Willowbend Blvd. # 310, Houston,
Texas, 77025 USA, (713) 668
4291 office, (713) 668 1724 fax, www.flameseal.com
© Copyright of Flame Seal Products, Inc. All rights
reserved, ® Registered Trademark of Flame Seal Products,
Inc., TM
Trademark of Flame Seal Products, Inc. |
|