             UL SymbolUnderwriters Laboratories Inc.  UL 100 Century Symbol
     

    May 13, 1994     
    .
    REPORT
    on
    FLAME RETARDANT COATINGS
    .
     Flame Seal Products, Inc.
    Houston, TX

 A not-for profit organization
dedicated to public safety and
committed to quality service.

Page 2                   Page 1                    Issued: 05-13-94        
              D E S C R I P T I O N
PRODUCT COVERED :
    The product covered by this Report is a fire retardant coating.
USE:

    The coatings covered in this Report are intended for use as interior coatings as permitted by the authorities having jurisdiction.  The established Surface Burning Characteristics of the coatings are applicable only when the coating material is applied in the indicated number of coats, coverage rates, substrates, and overcoats and undercoats as specified in the published advises of Underwriters Laboratories Inc. and when the coating is maintained.

COATING TYPE:

    This Report covers a fire retardant coating which was identified by the manufacturer as "FX-100®".

TP/MTC/scl


Page 3               Page T1-1 of 3                   Issued: 05-13-94
.
T E S T  RECORD NO.1

EXAMINATION OF MATERIAL:

    The material used in this investigation was produced in a ready-to-use form under the observation of a representative of Underwriters Laboratories Inc. and was applied to the indicated test surfaces at the manufacturing location.

    The composition of the coating material is of a proprietary nature and the formula involved is on file at the Laboratories for use in the Follow-Up Service Program.

    Various chemical and physical tests were conducted on the finished material.  The results developed from these tests were employed in establishing specifications for use in the Follow-Up Service Program.

SURFACE BURNING CHARACTERISTICS TESTS:

SAMPLES
.
Substrate

        Douglas Fir  -  The test decks were a nominal 22 in. wide and 8 ft. long, composed of 1 by 4 in. tongue-and-groove Douglas fir flooring fastened together on the unexposed surface with wood furring strips.  Three such decks were butted together end to end to form the 24 ft. long test surface required to fill the Steiner Tunnel furnace.

        Coatings

    The coating material was applied to the test surfaces by a representative of the submitter under the observation of a staff member of Underwriters Laboratories Inc.  The coating material was brush applied in one coat.  The amount of coating applied was determined by weight.

    One fire retardant coating was evaluated under this investigation and was identified by the manufacturer as "FX-100".  The coating was applied at a rate of 210 sq. ft. per gallon.

    The test samples were conditioned for 28 days at a temperature of 70 ± 5° and relative humidity of 45 to 55 percent before testing.



Page 4              Page T1-2  of  3                  Issued:  05-13-94
.
METHOD
    The tests were conducted in accordance with Underwriters Laboratories Inc.'s Standard  "Test for Surface Burning Characteristics of Building Materials", UL 723.
.
RESULTS
    Data on flame spread and smoke developed, results appear in  the following tabulations and as shown on Ills.  1 through  8:

Flame Spread:

    The maximum distance the flame spreads along the length of the sample from the end of the igniting flame is determined by observation.

    The Flame Spread Classification of the material is derived by determining the area under the flame spreads distance (ft.) versus time (min.) curve, ignoring any flame front recession, and using one of the calculation methods as described below:

        1.  If the total area (At) is less than or equal to 97.5 min. -ft  (meter-min.  x  3.3),  The Flame Spread Classification shall be 0.515 times the total area  (FSC = 0.515  At).

        2.  If the total area (At) is greater than 97.5 min -ft (meter-min.  x  3.3)  The Flame Spread Classification is to be 4900 divided by 195 minus the total area (At).  (FSC = 4900/(195-At)).
 
Test No.
Test Sample
Maximum Flame Spread
(ft.)
Time of Maximum Flame Spread 
(min. : sec.)
Calculated Value 
For Flame Spread 
Classification
1
Blank Douglas
Fir Decks
7.5
2:47
33.2
2
"FX-100"
3.0
9:47
6.2
3
"FX-100"
3.0
9:19
7.7
4
"FX-100"
2.5
9:29
6.8


Page 5               Page T1-3  of  3                    Issued:  05-13-94

Smoke Developed

    The smoke developed during the test is indicated by the output of a photoelectric circuit operating across the furnace flue pipe.  A curve is developed by plotting values of light absorption  (decreased cell output)  against time. The calculated value for Smoke Developed Classification is derived by expressing the net area under the curve for this material as a percentage of the net area under the curve for untreated red oak.
 
Test No.
Test Sample
Calculated Value For Smoke Developed Classification
1
Blank Douglas
Fir Decks
34.2
2
"FX-100"
18.6
3
"FX-100"
21.9
4
"FX-100"
23.1
TP

Page 6                                          Issued:  05-13-94

C O N C L U S ION

    The following conclusion s represent the judgment of Underwriters Laboratories Inc. based upon the results of an examination of tests presented in this Report as they relate to established principles in previously recorded data.

SURFACE BURNING CHARACTERISTICS CLASSIFICATION:

    The following Surface Burning Characteristics are established for the products submitted.

"FX-100"

.
APPLIED TO DOUGLAS FIR +
                Flame Spread   5
                Smoke Developed   20

 
        (+)(-)Tested as applied at a coverage of 210 sq.ft./gallon. Flash point of finished adhesive, closed cup: No flash to boiling.


Page 7                                           Issued:  05-13-94
 
    SURFACE BURNING CHARACTERISTICS OF APPLIED COATINGS
     

    FX-100 
    Douglas Fir
    Flame Spread 5
    Smoke Developed 20
    Number of preliminary coats None
    Rate per coat (sq. ft. per gallon) -----
    Number of fire retardant coats 1
    Rate per coat (sq. ft. per gallon) 210
    Number of overcoats None
    Rate per coat (sq. ft. per gallon) -----
    Flash point of fire retardant coating: 
    Closed cup, no flash

     

Page 8                                                      I11.1                                               Issued:  05-13-94
.
Flame Travel Results
FLAME SEAL # 01
UNTREATED DOUGLAS FIR DECK

Flame Travel Results - Test 1

            Flame Spread Index = 33.2
            Test Code = 04189401

Page 9                                                          I11.2                                            Issued:  05-13-94
.
Smoke Results
Flame Seal  # 01
UNTREATED DOUGLAS FIR DECK

Smoke Results - Test 1

            Smoke Index = 34.2
            Test Code = 04189401

Page 10                                                        I11.3                                               Issued:  05-13-94

Flame Travel Results
FLAME SEAL  # 02
COATED DOUGLAS FIR DECK
Flame Travel Results - Test 2

            Flame Spread Index = 6.2
            Test Code = 04189402

Page 11                                                     I11.4                                             Issued:  05-13-94
Smoke Results
FLAME SEAL  #02
COATED DOUGLAS FIR DECK
Smoke  Results - Test 2


            Smoke Index = 18.6
            Test Code = 04189402


Page 12                                                   I11.5                                            Issued:  05-13-94
Flame Travel Results
FLAME SEAL # 03
COATED DOUGLAS FIR DECK
Flame Travel Results - Test 3


            Flame Spread Index = 7.7
            Test Code = 04189404


Page 13                                                       I11.6                                              Issued:  05-13-94
Smoke Results
FLAME SEAL # 03
COATED DOUGLAS FIR DECK
Smoke Results - Test 3


            Smoke Index = 21.9
            Test Code = 04189404


Page 14                                                      I11.7                                              Issued:  05-13-94

Flame Travel Results
FLAME SEAL # 04
COATED DOUGLAS FIR DECK
Flame Travel Results - Test 4

            Flame Spread Index = 6.8
            Test Code = 04189405


Page 15                                                        I11.8                                              Issued:  05-13-94
Smoke Results
FLAME SEAL  # 04
COATED DOUGLAS FIR DECK

Smoke Results - Test 4

            Smoke Index = 23.1
            Test Code = 04189405