FIRE RETARDANT SPRAYS & FLAME PROTECTIVE SYSTEMS
FLAME SEAL PRODUCTS, Inc.
4025 Willowbend Blvd.
#310
www.flameseal.com
Houston TX 77025
USA
www.homefiresafetykit.com
(713) 668 4291 office
(713 668 1724 fax
Subject : Omega Point Laboratories Test
Report
"FX-100®
FIRE PROTECTIVE COATING" on plywood panels
The March 24, 1994 test was performed to show the fire performance of FX-100® COATING when applied to standard decking material (1/2" CDX PINE PLYWOOD) with a worst case scenario included which involved the primary flame impingement being a "joint" in the system. You will notice that there were six panels used, each 24 inches in length. This placed a joint at the point of contact of the test flame in the furnace.
Note that the test did prove similar performance as the U.L.
E-84
performed on Douglas Fir where the flame impingement was not at a
joint.
The intumescent expansion performed well in that it covered over the
small
gap at the joints. The flame spread was almost identical to the
U.L.
test with the only difference being that slightly more smoke was
evolved
from the test sample when the joint was first exposed to the flame as
the
heat affected the ends of the test pieces until sufficient intumescent
expansion insulated the material.
Michael D. Kiser
Research & Dev..
March 24, 1994
.
Prepared For:
.
Flame Seal Products
4025 Willowbend Blvd. #310
Houston TX 77025
Report No.
14770-96872
Page ii or ii
Flame Seal
Products
March 24, 1994
SURFACE BURNING CHARACTERISTICS OF BUILDING MATERIALS (ANSI 2.5, NFPA 255) Test Date: March 23, 1994
|
The description of the test procedure and specimen evaluated, as
well
as the
observations and results obtained, contained herein are true and
accurate
within the limits of sound engineering practice.
.
Omega Point Laboratories, Inc. authorizes the client named herein
to
reproduce this report only if reproduced in its entirety.
The test specimen identification is as provided by the client and
Omega Point Laboratories accepts no responsibility for any
inaccuracies therein.
Executive Vice President
Report No. 14770
-96872
Page 1 of 6
Flame Seal
Products
March 24, 1994
I. INTRODUCTION
This report describes the results of the ASTM E84-91a Standard Test Method for SURFACE BURNING CHARACTERISTICS OF BUILDING MATERIALS (1), a method for determining the comparative surface burning behavior of building materials. The test is applicable to exposed surfaces, such as ceilings or walls, provided that the material or assembly of materials, by its own structural quality or the manner in which it is tested and intended for use, is capable of supporting itself in position or being supported during the test period.
The purpose of the method is to determine the relative burning behavior of the material by observing the flame spread along the specimen. Flame spread and smoke density developed are reported, however, there is not necessarily a relationship between these two measurements.
"The use of supporting materials on the underside of the test specimen may lower the flame spread index from that which might be obtained if the specimen could be tested without such support... This method may not be appropriate for obtaining comparative surface burning behavior of some cellular plastic materials... Testing of materials that melt, drip, or delaminate to such a degree that the continuity of the flame front is destroyed, results in low flame spread indices that do not relate directly to indices obtained by testing materials that remain in place."
This test method is also published under the following designations:
____________________
(1) American Society for Testing and Materials (ASTM), Committee
E-5 on Fire Standards
II. PURPOSE
III. DESCRIPTION OF TEST SPECIMENS
Specimen Identification: "FX-100®"
Intumescent Fire Retardant Coating
Specimen Description:
The test sample consisted of six plywood panels, coated by Flame
Seal Products with "FX-100" at a spread rate of 150 sq.ft./ gal.
The panels each measured 24" x 48" x 1/2". The sample was
delivered
to the test laboratory on the test day, per client request.
Report No.
14770-96872
Page 3 of 6
Flame Seal
Products
March 24, 1994
IV. TEST RESULTS
The test results, computed on the basis of observed flame front advance and electronic smoke density measurements are presented in the following table. In recognition of possible variations and limitations of the test method, the results are computed to the nearest number divisible by five, as outlined in the test method.
While no longer a part of this standard test method, the Fuel
Contributed
Value has been computed, and may be found on the computer printout
sheet
in the Appendix.
|
|
Index |
Developed |
| Mineral Fiber Cement Board |
|
|
| Red Oak Flooring |
|
|
| "FX-100®" Intumescent Fire Retardant Coating |
|
|
The data sheets are included in the Appendix. These sheets are actual print-outs of the computerized data system which monitors the ASTM E84 apparatus, and contain all calibration and specimen data needed to calculate the test results.
V. OBSERVATIONS
The coating became intumescent at 0:08 (min:sec). Sample ignition was observed through the tunnel windows, and occurred at approximately 0:30 (min:sec). Char formed a thickness of 1" at 1:00(min:sec), 1.5" at 1:15(min:sec), 2" at 2:05(min:sec), 3" at 3:25(min:sec), and 4" at 4:15(min:sec). Maximum flame spread of 2.0' occurred at 9:46(min:sec).
After cooling and removal from the tunnel, the specimen was observed as follows: The coating was intumescent to 24', and was approximately 3" thick. Channels had formed in the intumescent coating at 2', 4', 6', 8', 10', 12', 16' and 20', thus exposing the substrate (plywood) and allowing char to form on the plywood. Partial consumption of the plywood was noticed between 4'and 5'.
APPENDIX
DATA SHEETS
Client:
Flame Seal Products, Inc.
Date:
10:24:14 03-23-1994
Test Number: 1
Project Number: 14770-96872
Operator:
CGH/ SR
Material ID:
"FX-100® "
Intumescent Fire Retardant Coating
6 panels @ 24" x 48" x 1/2" - of plywood coated with "Fx-100®
Coating"
@ spread rate of 150 sq. ft. / gal.
TEST RESULTS:
| Time to Ignition = | 00:00 (Min:Sec) |
| Time to Max FS = | 09:46 (Min:Sec) |
| Maximum FS = | 2.0 (Feet) |
| Time To 980 F = | 980 F Not Reached |
| Max Temp = | 633 (deg. F) |
| Time To Max Temp = | 09:55 (Min:Sec) |
| Total Fuel Burned = | 50.87 (cubic feet) |
| FS*Time Area = | 11.3 (Ft*Min) |
| Smoke Area = | 44.3 (%T*Min) |
| Fuel Area = | 5665.2 (F*Min) |
| Fuel Contributed Value = | 14 |
| Unrounded FSI = | 5.8170 |
CALIBRATION DATA . . .
| Time to Ignition of Last Red Oak = |
00:38 (Min: Sec) |
| Red Oak Smoke Area = | 117.49 (%T*Min) |
| Red Oak Fuel Area = | 9106 (F*Min) |
| Glass Fiber Board Fuel Area = | 5086 (F*Min) |
PROJECT NO: 14770-96872 Time & Date: 10:24:14 03-23-1994

| ADDRESS:
FLAME SEAL PRODUCTS, INC.
4025 Willowbend Blvd. # 310, Houston, Texas, 77025 USA, (713) 668
4291 office, (713) 668 1724 fax, Website: www.flameseal.com
Email: flameseal@flameseal.com |
| PRODUCTS:
BARRIERS: | FBS Wrap -Cables, Conduits, Flanges | FBS Panel -Walls | LIQUIDS: | Wood | Leather | Fabric | Coating | Plastic | Paper | Wild Fire Coating | GENERAL | Prices | Product Description | Products | Testing Info | MSDS Index | In the Lab - NEW PRODUCTS ! | Privacy Policy | ( Investment: | Stock News | Transfer Agent | ) |